E2660-CO-NO2

CO-NO2 Transmitter
E2660-CO-NO2
Features
  • Simultaneous CO and NO2 monitoring
  • Two analog outputs 4-20 mA / 0-10 V
  • RS485 Modbus RTU digital interface
  • Wall-mount IP65 protected housing
  • Two SPST relays, acoustic alarm
Description

CO-NO2 detector-transmitter E2660R-CO-NO2 is  an easy-to-use instrument intended for simultaneous monitoring of carbon monoxide and nitrogen dioxide concentration. It is an excellent solution for underground parkings. The device may be also used in boiler houses and other confined spaces, where potentially toxic concentration of carbon monoxide and nitrogen dioxide can accumulate.

The instrument utilises novel fully calibrated and temperature compensated electrochemical gas sensors with excellent repeatability, stability and long lifetime.

Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the transmitter to safety or building automation systems.


Technical Data
Sensors type Electrochemical cell
Sampling method Diffusion
Detection ranges 0...100 ppm CO
0...20 ppm NO2
Resolution 1 ppm vol CO
0,1 ppm NO2
Sensor lifetime > 2 years
Calibration interval 6 months
Power supply 12...36 VDC (default),
24 VAC or 230 VAC as options
Analog outputs two 4-20 mA / 0-10 V (user settable)
Enclosure grey ABS plastic, IP65
Dimensions H90 × W145 × D50 mm
Operating conditions -20...+50 °C, 15...90 %RH


Similar Products


E2660-CO-CO2 - CO-СO2 Transmitter
E2660-CO-CO2 - CO-СO2 Transmitter
  • Simultaneous CO and CO2 monitoring
  • Range 0...300 / 1000 ppm CO and 0...10 000 ppm CO2
  • Resolution 1 ppm CO and 1 ppm CO2
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485

E2660-CO-NO - CO-NO Transmitter
E2660-CO-NO - CO-NO Transmitter
  • Simultaneous CO and NO monitoring monitoring
  • Range 0...300 / 1000 ppm CO and 0...250 ppm NO
  • Resolution 1 ppm CO and 1 ppm NO
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485